In this episode, Bryan and Ty take on one of the trade's favorite rules of thumb. It can be a reasonable starting point for many systems under moderate, near-sea-level conditions, but it is not a universal target. Proper airflow depends on actual delivered capacity, sensible and latent load, air density, climate, manufacturer data, and what the system is supposed to accomplish - not just the tonnage stamped on the cabinet.
They explain why dry-climate and high-altitude applications may require more volume airflow, why humid applications often use less coil airflow to improve moisture removal, and why mass flow matters more than volume alone. They also cover nominal versus actual capacity, suction-line pressure drop, equipment-specific performance at 208 V, Manual S and expanded performance data, and field verification with measureQuick and the TrueFlow® Grid.
The takeaway is simple: use the rule as scaffolding, then measure the system and follow the equipment data.
This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, NAVAC, and Filtrete.
Resources:
Not All CFM Are Created Equal
Impacts of Decreasing Evaporator Airflow
Troubleshooting With DTD
AHRI Data vs. Manufacturer Expanded Performance Data
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
The HVAC School Podcast is made possible by these great sponsors. Refrigeration Technologies and their Viper Aerosol Coil Cleaner for condensers and evaporators. If you don't know, the Viper Aerosol Cleaner is a foaming cleaner that you can spray into a coil with its really powerful pin spray. It has a strong degreasing capability in a convenient package. It's safe to use with rinsing or no rinse,
so there's zero need to bring a bulky pump sprayer into the house for an evaporator coil cleaning or in many refrigeration applications. And like we mentioned, it works on evaporators and condensers. Find out more at refrigtech.com. Carrier and Carrier.com. Carrier has been a long -term sponsor of the podcast. They've made it possible very early on for us to do what we do, and they are the products that we sell day in and day out, everything from single -stage equipment all the way up to the green speed extreme,
one of the most efficient products on the market today. Find out more about what Carrier has to offer and about becoming a Carrier dealer by going to Carrier.com. NAVAC at NAVACGlobal.com. Filtrete air filters at Filtrete.com. Filtrete has been going above and beyond other filter manufacturers because it rates its filters effectiveness in capturing even microscopic particles. You'll see a MERV rating and an MPR rating on the packaging. MPR stands for Micro Particle Performance Rating, and it rates how well a filter
can capture tiny particles like smoke, bacteria, and more. Filtrete filters are designed with pleated media that maintains similar airflow levels across MERV ratings 8, 11, and 13. According to data published by the California Energy Commission, Filtrete's 1900 MPR MERV-13 filters have the highest airflow rating among available residential 1-inch MERV-13 filters. Learn more about Filtrete's filters and standards at HVACRSchool.com/Filtrete.
He's got more airflow opinions than most people have tools. It's your host, Bryan Orr. Yo yo, yo yo yo, what's up? My brothers and sisters in the HVAC trade. Thanks for listening. This is the HVAC School Podcast. I'm Bryan. Bryan Orr, if you must know, and my name is spelled with a Y and my Orr is spelled with two R's. And, you know, if you hang out with me, you'll never be up a creek without an Orr. Wow, that's rough. And it's always rough when Ty and I talk.
There's lots of dad jokes, although not too many in this episode, frankly. But Ty Branaman of Love2HVAC, great guy, one of my very good friends in the trade and somebody who helps us at The Grit Foundation. Find out more at TheGritFoundation.com. When I say he helps us, honestly, he does all the work. Ruchir Shah and I came up with the idea and put together the structures, but Ty is the one who goes to the camps and makes them real and helps lead education for what we do at The GRIT Foundation. So check that out. See if you want to be part of it or if you want to support. We would always appreciate that.
We have a lot of really great people like Eric Kaiser. It's always helping out at Grit camps. Danny Mulzitt is another one who comes to mind, who's helped out a lot. Lots of really great guys who make it possible. Guys and ladies. I don't know why I'm just saying guys. So many people. Sue with TruTech Tools has put on a couple camps. She does a great job with it. So many great people who have helped out with that. But that's not what we're talking about today. Today, we're talking about 400 CFM per ton. That rule of thumb, where it works, where it doesn't, where it came from, and then how to think about times that you need to adjust
it. We're not going to talk through any boring math here. We're just going to kind of riff on it a little bit. Ty and I talking about 400 CFM per ton. Ty, how the heck are you? Doing great. Life is a breeze. Life is like a box of disgusting dark chocolate. You do know what you're going to get and it's going to be disappointing everything. Just kidding. It's like a breeze in a 130 degree attic at 90 % humidity. It's like a breeze coming off of an exhaust fan from the bathroom of a w***.
We're talking about the whole CFM per ton rule of thumb, the good old rule of thumb. So what is that rule of thumb that oft gets repeated, Ty? Oh, man, 400 CFM per ton. The rules and oh, it pains me so much. Of the rules of thumb, at least it has some valid cores to it. I like how Alex Meaney explains it. He's like, look, we're going to put this brick here. It's not a brick, but we're going to put this to hold a shape and we're going to come back later and replace it. And so many people have used a 400 CFM per ton. We've put that in there and we just thought that that was like an actual brick.
And it's like, no, no, we need to replace that with some more details. That's what we're going to talk about today. We're going to use Alex Meaney's beautiful example there. We're going to take that holder out and put an actual brick in there that you can leverage on. Yeah, the term that Dick Wirz uses in his book is rot, or I think he calls them trots, but I always do rot. Rot is a rule of thumb. The problem with a rule of thumb is it's like wood. It's good, but then eventually it's going to rot on you. It's not always going to apply. And that's the case here, too. 400 CFM per ton is just a rule of thumb. It's a starting place.
It's something that helps you build that. It's a scaffolding that you build around, but eventually it doesn't stand up. So let's start with the basics here. We're going to talk about where it actually can be pretty accurate and then where it gets increasingly inaccurate. So let's talk about first, why do we say it in the first place and why is it sometimes does apply actually? Well, you're talking about standards. You have to test of a piece of equipment and you have to test it under a set of standards. So you have to come up with some hard rules like, hey, we're going to test this under these basic rules. And in those rules, what are we going to have for airflow?
Let's set 400 as our CFM. So now we know the outdoor temperature, the indoor temperature, and the humidity, and how much air we're moving across the coil. So that gives us a good test point. And under those test points is also where you get the magic 40 degree evaporator, because under those test conditions, that's what your evaporator will be. Not that that's what it's going to be all the time, but that's where that comes from, basically from the initial testing. And it also just makes sense. There are limitations that we have in compression refrigeration in the types of equipment where we're air to air types of equipment, because we don't want our evaporator coil to drop below 32 degrees.
Correct. So we can't have airflow so low that it drops below 32. And we still want our coil to be below dew point in most cases, in most green grass markets. So that way we can drain some moisture out of the building. And so somewhere in there is a level of airflow. And 400 happens to be right in the middle of that, where you're condensing moisture on the evaporator coil, and you're not freezing it up. We can't run our evaporator coils with too low of airflow for lots of reasons, even if we wanted to from a de -emitification because of freezing. And if we run too high of air flows,
you will hit a point where that evaporator coil is no longer making water. Making water. But again, that's under normal green grass conditions, what we typically see, typical sea level situation. That 32, once we get our saturated temperature below 32, that's what I call the Hans effect. We want to keep away from that, because that's Hans so low that it's going to freeze up. Did you just think of that just now? You said so low earlier. And I was like, I couldn't hear anything you said. I was like. Right. You're just looking for a way to shoehorn that in there. That's all it was.
100%. Yeah. So talk about cases where you're running into really dry conditions and cases where you have higher altitude and how that can affect what your targets would be as far as airflow. Two huge things. One thing that's really benefited me is how many different places I've lived. So I've lived in Miami. I've lived in Texas. I've lived in Phoenix and Nevada. So I've lived in Australia. So I got to see a lot of different climates. And so it's been huge and changing my thought process of this is the number that you need. So in Las Vegas, it's dry.
You don't need dehumidification at all. Like it's that one day that it rains. So most of them, you don't need dehumidification. Your air is already too dry as it is. A lot of the singers there have humidifiers in the middle of summer. They're humidifying to keep their voice good so that they can continue to sing. So how do you prevent dehumidification? More airflow. And more airflow makes the system efficient if you're considering sensible heat only, sensible capacity. So having more airflow is good. So yeah, we can get the cold temperature up moving more air.
Take exchanging heat at a much faster rate. It makes everything more efficient. The air is moving through the duct in the attic so fast you're not losing as much heat. So it's just all around a great win for that. So we're looking at much higher. 450, even 500 CFM per ton. That's a great thing. The duct work has to be able to handle that too though. But there's no reason to have your coil at 33 degrees in Las Vegas and trying to pull a little bit of water out of the air as you can. Now you've got this low-temperature air traveling slowly through this duct work. You're having a lot of heat gain in it.
It's just all around loss. So in that condition, then yeah, hey, let's speed the air up. Make sure the ducts don't handle it. Speed the air up and just everybody wins on it. But like you said, also we have the altitude. And what's cool about Las Vegas is you have Death Valley right around the corner of that sea level. Las Vegas is 2000 feet. And you got Mount Charleston, which is a 45 minute drive. That's 8 ,000 something feet elevation there. So you have like all of this going on at the same time. And a friend of mine, Mike Lindsay in Las Vegas, he does, he's a lab technician his whole life.
HVAC specialist, complete nerd, love him. And he does this testing with airflow and he goes out into the desert in his spare time and he sets up all this gadgets at sea level, finds the exact sea level and does all the testing with different weather conditions. And then he goes up to like Mount Charleston and he does all the testings at altitude to see for himself, like how weather changes and how different temperature and humidity changes all of his numbers. And he tests different ways of measuring air. And that's where I really learned about the difference between SCFM and other
CFMs. Actual, yeah, actual CFMs. And I still get them mixed up because I don't do it daily enough to keep it lined up. But when he starts talking about capacity of a system and how, hey, we're moving so many CFM of air, but because the air is a lot thinner, even though you're moving so many cubic feats of air, you're not moving as much volume of the actual molecules. So you're not changing as much heat. So it changes the entire capacity of the system. And it just blew my mind that he had to change the ratings of the system to account for the airflow. And I just never done it.
We just, hey, it's a four ton, we install it. And so he changed my entire thinking about CFM capacity, all these other numbers. So being in Vegas was huge for me because I got to see a bigger side of it. Yeah, because it isn't a directly linear calculation. It gets actually pretty complicated. So let's see if I can basically explain this without boring everyone with numbers. When we say SCFM, it's essentially locked in at the density of air at sea level. So you're pretending as though, if I'm moving 400 CFM at Death Valley and I'm
moving 400 CFM at the top of a mountain, that it's moving the same density, the same pounds of air, but it's not. And so that's the thing. We could be moving, and I like how Jim talks about it as boxes of air. I've always used that. And so if you're moving 400 CFM at altitude, you're moving the same number of boxes. The boxes just don't weigh as much. And what does the coil care about? The coil cares about the weight of the air much more than it does the boxes of air. But the thing is, is that you, then you also have the speed of the air. So if you just try to move more air to do the same,
so all we got to do is just move more air over the coil. The face velocity across the coil is still proportional to the actual volume of the air. So now you have more molecules, technically, because you're rushing more paths, but they're going faster. And so now you're dealing with face velocity across that coil. And if you're thinking about that boundary layer of these little air molecules touching the metal in the coil, just moving more faster doesn't necessarily get the same proportional result. It's not like you can just graph that with a basic linear chart. And so the point is, is that it's harder to move heat into air or move it out
of air into a coil in altitude makes perfect sense. We also have density adjustments that happen at different humidities. It's not as nearly as significant as altitude, but it does. Air that is more moist is actually a little bit less dense. And so it's the same thing to a much lesser degree. A lot of people think that's wrong because they think of air as being heavy. And every time I have to do that in my head, it's like, I don't know, but actually water vapor is less dense than air. And I know some people are going to say, he's wrong, you made a mistake. I'm not talking about liquid water. Liquid water is obviously more dense than air,
but I'm talking about water vapor. That's why water vapor rises. That's why we have clouds. So there's all these little controlling factors. And so when we say SCFM, we're just locking it in at sea level and pretending it's the same everywhere. And the result is, is that when you have some of these various conditions, a lot of times you do need more airflow to do the same work and sometimes significantly more airflow to do the same work to get the same pounds of air over that coil. That's the beautiful thing about what we do. Like Willis Carrier, when you look at the psychrometric chart, he was able to map the air.
And because he can see what the air is doing, then he can see what happens when he modifies it. And so all of these engineers and scientists have done so much this work before us. And they've given us these parameters to work with. And it's cool, funny equipment. Most people never looked at what the actual rated capacity is and then how that capacity rating changes under these different conditions, under different humidity, under different indoor and outdoor temperatures, different humidity, all of that. But they've charted us all out for us. Now, when you have that chart, it's all digital now because we used to put the
chart we had to put it in a pocket and that was bad because you would have a chart in your pants, you never wanted that. But now you can have your chart on your phone and you can look up this data and you can see what it's going to do under the conditions. So if I'm installing one at altitude in a dry climate, in a humid climate, what is that equipment going to produce under these conditions? And then we can compare and know, hey, what are we trying to solve? Which equipment is going to do that? Because a four tons is not a four ton system. And that's actually a really good point. There's a couple of different ways in which when we say 400 CFM per ton,
we're making a simplification on several different sides. And that's where it's not bad. It's just very inaccurate. It's using a very dull knife to cut with. And so we've talked a little bit about how air isn't always SCFM. And so if the altitude changes, humidity changes, temperature changes, those are all factors. We also talked quickly about how in some markets you actually want higher air flows because you don't want to be wringing moisture out of the air. That's the high end of that. We started by saying you want to be in the middle somewhere between freezing but also below dew point, unless you're in an arid climate where you actually
don't want any moisture taken out of the air. So we mentioned that and that's all on the air side. But then on the equipment side, it's also a moving target. And that's what you just said. If you have a four ton system and we're assuming that it's 48 ,000 BTUs per ton and it's a certain number of CFM per ton, what's actually more accurate is the number of CFM per BTU. That's actually a more accurate way of doing it. And it's even more accurate if it's actually a pounds per air per BTU. That's actually when you're now we're starting to dial it in. And again, you could have a 48 ,000 BTU piece of equipment and based on the exact
match of air handler and condenser, it could be 46 ,000 BTUs. Then you have the actual conditions that it's operating under. Maybe it's higher temperature or whatever humidity is different. Now that can de -rate. And then you could have all we actually went down to a three quarter instruction line, which is actually allowed, but it actually de -rates the capacity a little bit. Okay, now that de -rates and oh, actually it's in a commercial space. So it's on 208 volts instead of 240 volts. And now that de -rates a little bit. And so you could have a four ton system that ends up being 38 ,000 BTUs by the time you have all of these de -rating factors.
And so what's more important is not that it's four tons, it's that it's 38 ,000 BTUs. And it's not 400 CFM per ton. It's a particular number of pounds for that climate of air per, what did I say, per BTU of system operation actual. So actual BTUs operation. And that's where it gets really, really useful because you're going to hear this and like, well, how the heck can we do that? That's where tools like measureQuick or great because it can help correct for all of this. It can correct for both sides of that equation and tell you whether you're in an acceptable operational range or not based on the real rated capacity
of that equipment under these conditions, not just the nominal capacity that you read off of a model number. All right, going to take a second to talk to you about Refrigeration Technologies' WETRAG. It's a product that our techs have used for a long time. Works great. It's a heat blocking putty that works just like a wet rag. You put it around valves while brazing, put it in a valve inlet, your service valves, your evaporator, your service valves, your reversing valves. If you're replacing a reversing valve, heaven help you, but this really works great for that. TXVs, electronic expansion valves, reusable up to 40 times with dye that lets
you know when it's nearing the end of its life. Easily withstands our torch temperatures and protects things like we talked about compressor, paint, reversing valves, line driers, suction driers, liquid line driers, bi-flow driers, basically all the dryers. It's great for dryers, especially the ones with the really short stubs. Pain in the butt. You don't want to burn that paint. You don't want to create rust on those new dryers that you put in. All you have to do is take it out, put it around anything you want to protect, then put it back in the container to reuse it.
For larger areas, we've talked about this a lot, Refrigeration Technologies also has introduced the HeatShield which you can use wet or dry and cover a larger area like the front of an air handler or a case evaporator coil, for example. Also great for air-acetylene or swirl tip torches or they tend to blow out a lot more heat on the convective side. Works great for that. Find out more about the original WETRAG as well as heat shield by going to refrigtech.com Now, I just want to make a little pause here because if
I'm talking to me many years ago, I'm like, you're going way too deep. You don't need - This is way too much, right? Exactly. So as an example, it is relevant. Let me put some relevance to you. There's these things called these Chinese diesel heaters. So people that do off -grid living, they put the Chinese diesel heater in because you get the most heat out of that diesel fuel to heat a camper than you do with propane, which is cool because people in these groups have talked about the density of the two, the propane versus the diesel, which is like cool nerd stuff. But they also talk about when you go into altitude, how the altitude affects, how these burners work and how these little kits that
people have gone in and solve these problems. So it's a real problem that people solve. Same thing with generators. People have generators. They go up in the altitude because the air is thinner. They're generated and put out the performance they need and they have to get a bigger generator to offset this or reset up the generator to work at that altitude and then do it again and then get debt back down. So the reason I'm talking about that even though it's off topic is it's relevant. And if it's relevant to people that aren't engineers and scientists and professionals that do that for a living, just people that do it on their own to figure these things out, it's absolutely relevant to us who do this on a day -to -day basis.
And there's people that move all over the country. You may live in this one climate and then you move to Vegas. There's people that have moved from Florida to Vegas and understanding the difference in the air and air weight and how that capacity works or somebody who finally gets their dream to move to the mountains or moves from the mountains down the sea level. These things all play a part. They all act together. So all these things we're talking about, we're talking a lot of numbers now, but they're so important when you have the appreciation of what we're doing, having an appreciation for seeing a psychrometric chart and thinking, man, I don't understand this, but I want to.
So we're talking about these SCFM and the weight of air and how much heat we're moving. It's awesome. It's really cool to think this has been mapped out for us and it's been done and simplified to things like measureQuick so we can easily communicate to that red, green, yellow dials telling us how many BTUs of heat removing sensible and latent, how many pounds of water removing out of the air every hour. The whole entire book of Psychrometrics Without Tears is pretty much put into pictures and live data with measureQuick. Yeah. And again, like, where does it matter?
It matters in a lot of cases. As a technician, you're not going to typically do a ton of math, but you need to know where to do the math when it's time to do the math and you need to know how the tools basically do what they do and that's where you're working at altitude. Remember to remember, remember to stop and be like, okay, this is going to be different than when I was in Miami. I'm going to need a little more air to do the same thing or my oxygen levels are going to be lower when I'm doing combustion or whatever the case may be. That's a good example of it. But another really good example is if you're moving from markets where humidity control isn't that big of a deal and then you move to a market like Florida or
you move to a market like Louisiana or areas in Mississippi or South Carolina, areas that have a lot of latent load. We're very concerned about moisture load in houses because we're trying to keep people comfortable, but also really trying to keep suspicious growth from showing up in different places. I'm trying to learn my lingo here, suspicious biological growth. That's actually what Florida wants us to say specifically. They tell us suspicious biological growth. That's the phrase because we want people to be healthy. So we want to be comfortable and healthy. And so the strategy that's been used for a long time and is still today is we
reduce that CFM per ton. But what is it really? We're moving fewer pounds per BTU. And so if we think that we're running 350 CFM per ton but we're not taking into account that derating of the equipment, we may actually be running 400 CFM per ton when we're trying to run 350 because 350 to 325 is a typical target in our market for good solid latent removal and sometimes even a little lower than that for short periods of time. You can get down to like 290 in some cases, unintentionally in a lot of cases. But here's where it gets interesting in our market.
And I was just like my favorite topic. So just bear with me here for a second. Is it the less airflow that you run over that coil, the less pounds that you run per BTU, the colder the coil is and the colder the discharge area is out of the top of the unit. Well, that has other consequences. Where is that unit located? Is it located in a humid location where it's going to start sweating? Okay, well, that can be a suspicious growth problem in and of itself. Is the duct work going to start sweating? Are the vents going to start sweating? All of these different factors. And so a lot of times with the way that we currently do it, even to this day, we solve a problem because we're pulling more moisture out
of the house. But we create a problem by making ducts sweat, vents sweat, unit sweat. And what we've talked about a little bit lately, just for fun because there are actually some people who design it this way is you could really design systems where the airflow stays constant. Meaning the amount of air that the blower moves through the vents stays constant. And what you vary is the amount of air moving across the evaporator coil because that's actually what matters in terms of moisture removal. I actually saw that in your group chat that you had. That's Michael Housh's brilliance. I get blinders on. I start looking at equipment. So we're talking about manual T with Reagan and the vent throw.
And he's like, well, it doesn't matter because we have once we slow the flow of air down, manual T is out the window. And I'm like, I think it's important still because people don't appreciate the throw at all. But it had a valid point. And then Michael Housh has brought this up in the past. And I forgot about it. He's a brilliant man. But you don't know him. But he was talking about keep the airflow constant so that you don't have that issue. Like, well, yeah, you keep the airflow constant. You don't have to worry about the ductwork sweating. But now you're not going to dehumidify. And I'm like, it just obviously that's not going to solve the problem. You're not going to dehumidify because I was thinking equipment and he's like,
no, obviously air bypass. And I forgot he had the Frankenstein system where he designed it where you could keep the air going to the coil separate decoupled I think is the cool word he used from the rest of the air so he could keep his airflow up, keep his volume up and still have the dehumidification factor. And I was like, man, that is really brilliant. It just brought me back out to the bigger picture of the house as a system. But then it comes into like how we're going to make this repeatable and get it. But that's how my brain works. It's like, oh, this is a fun thing. But then you can run down these rabbit holes. But it's really awesome to think, hey, we want to slow the air down so that we
can dehumidify it. But keep the volume of air up so that we don't sweat in the ductwork. And that's what I love about this trade. There's never like, oh, just do this and we'll solve the problem. Sometimes it will. Sometimes it creates a new problem. And it's cool to have friends that educate you and get you thinking outside of that box that I get stuck in sometimes. Yeah. And again, because I remember the first time somebody brought this up to me, this design, I saw it, somebody had specced it. And I was like, oh, that won't work. And I was like, wait, why won't it work? And then I realized I was wrong because I was thinking like, I don't know what I was thinking.
I was thinking it was going to like grow mold inside the ductwork or something. But then you're like, oh, no, mixed air conditions. No, this actually works just fine. And the point isn't that because this is what I think a lot of people get frustrated with me in the nerd community about. You can be a purist where you're like, if you don't know this, you don't deserve to carry tools. And it's like, I don't think that at all. And I think it's great guys who are early in their career and they just follow best practices and they're learning as they go. I think that's great. You don't necessarily have to understand all this stuff in order to be a good tech. But the more you do understand, the better problem solver you can become.
And so now when you run into this really weird situation, a really tough situation where humidity becomes very important, whatever the case may be, now you have an extra tool in your arsenal that you know you can use to help solve that problem. You understand it a little bit better. That's where this comes in really handy. If you live in Ohio and you're setting up equipment at 400 CFM per ton and you're measuring it with TrueFlow Grid and you're going off the nominal capacity, you're not doing all these derating conditions and all this, you're probably not that far off. It's not the end of the world. It's going to be better than almost any. But if you can drill down and you go to the expanded performance data on your
equipment, instead of saying four tons, you say 42 ,000, 43 ,000, 44 ,000 BTUs, whatever it is based on the actual rated conditions. Well, then you're going to be a little bit better. And then if you understand about air density and the difference between SCFM and measured or actual CFM, you're going to be a little bit better. You're just sharpening that knife a little bit more. And it's not so you can be cocky and walk around with your chest pumped out at the symposium and tell people how good you are with airflow. That's not the point because it just makes you understand what you're seeing a little bit more. So I frequently talk with Chris Hughes and Steve Rogers.
And Steve Rogers is just brilliant a level that sometimes I can't grasp. And then it's almost annoying sometimes. He's like, it's like such a high level. But then I want to feel smart too. This isn't fair. But then Chris is able to like take that is like, okay, let me translate this as a technician talk. I'm like, all right. And then we have these fun off the wall conversation. Well, what if we did this? And what if we did that? And it's fun to exercise your mind and think outside of, hey, we got the system back up and running. When I first got into psychometrics, I was having so much fun solving problems
with psychometrics. I thought I was a superhero that was out doing stuff and I had this one house. The humidity was high in the house and the customer is blaming the equipment and the guy with the equipment was like, no, it's right. It's whatever. So they were able to go through and find the capacity of the equipment under the conditions that we had. It's like, here's what it's performing. Here's what it's designed for. I ran my psychrometric chart, which does what measureQuick does automatically now. We had to do this, but I did all the old school math. Like, man, this thing is dehumidifying great. We measured the airflow. The airflow is down as low as it can go and we're dehumidifying like crazy.
So I had them call an energy auditor out. They did a blower door test on the house because technicians didn't have that available then. And they said, nope, the house is pretty tight. Here's your leak points, et cetera, et cetera. But with the outdoor humidity, wasn't really the problem. So I came back out, crawled into the house and found there's a water leak. So the water was leaking and coming up through the floor and that was where all the humidity problems was. So we were looking at all of these other things and the problem was outside of the box. And so it's fun though when you start thinking outside the box and exercising it, then you can solve more problems.
So we're thinking about airflow. My big thing is, can you actually measure it? And using the blower curves are nice, but only if it's a factory motor and the factory wheel and there's some conditions. There's a lot of other ways with using the hot-wire anemometer going in, but people don't realize you have to actually traverse the ducts and do all the different points, which is math. And I don't like math because they get numbers mixed up. But now we have the TrueFlow Grid. And I realize a lot of people can't afford that. I had to save up for over a year to buy mine. So it was a huge investment, but it's probably the best tool I bought because I could actually ideally quantify the airflow, check the airflow,
know exactly how much airflow I had with measureQuick. I can find out what my system is doing and with the performance chart of the system, I could find out what that system is capable of moving under those conditions. And I can say, hey, I'm moving exactly what I'm supposed to and BTUs of this airflow. BTUs, sensible and latent. My system's good. Now let's look outside. Duct leakage, house leakage. What are my problems coming from outside of the equipment? And it's fun being able to solve that, but understanding airflow. Oh, just slow the blower speed down. It'll solve all your problems or create a new one.
Now we have moisture happening in the attic. Now the unit sweating like crazy. And then somebody just tagged me recently is like, hey, Ty, can you do a video explaining what this guy's problem was? I was like, no, because I need to go out there or he needs to give me more information because we can't just say the unit's condensating. We need to do X, Y, and Z. No, let's test. Let's get some data. And with more information, I can make a better decision. Yeah, and it does make it so much easier. I mean, you can do and I actually suggest that at least a few times you do some of these calculations longhand and all that. I mean, it's perfectly good thing to do,
but nowadays we have tools and that's what measureQuick is. It's an amazing tool to help us do the math and come to the right conclusions, taking into account all these different factors. TrueFlow Grid. Same thing. Excellent tool. But yeah, you can get a test hotwire anemometer and do some measurements there. I mean, you can do branches, so you can do other cool things. It's really fun. I mean, I did a lot of that and it's a blast, but you got to learn how to do it because it isn't straightforward. It isn't just one measurement. A lot of people are like, well, just take measurements with the flow hood. It's like you'd be shocked how inaccurate flow hoods can be even. So these are all things around measuring airflow.
If you want to learn more about this, watch any of Bill Spohn's great presentations on airflow measurement. TEC does a lot of really great presentations on this as well. But go back to some of the old symposium videos and watch some of those because we're not going to cover all that. But the point here is, it is a bit of a moving target based on real site conditions, based on the weight of the air, like we talked about, versus just the boxes of air and based on the particular equipment and the actual rated capacity of that equipment with all the factors included. And some of those factors are variable with weather and some of them are not
variable. If you're up in the mountains, it's going to be in the mountains its whole life probably unless somebody sells it used on Craigslist or something. So it's going to be under the same conditions. So set it up for those conditions. If it's set on 208 power, in some cases, not all equipment, but in some equipment, it does actually derate. Not only it doesn't just change your current and your SEER rating, but it also changes your actual capacity of the equipment in some cases. So the motor actually slips more and runs a little slower if it's a PSC motor. It's kind of wild. Think about that. And so those are all factors. Read again, all comes back down to reading the Fantastic Manual and being curious
enough to find out about the equipment. But I'm really looking for it is, I don't know, I think I told you this, August is my in the field month. And this is one of the first things I'm really excited to do because at Kalos, we use a ton of TrueFlow Grid grids now and I came out of the field before that era. And so I'm excited to get out there and show everybody and learn myself about all the different ways you can use it to find problems rather than just we do it mostly on sales and some on commissioning now. But I really want to get us doing it more because I think it has a lot of benefits. All right. So NAVAC has some great vacuum pumps and hand tools,
but I'm also a big fan of their cordless power tools for bending, flaring, and swaging copper quickly and easily. NAVAC's three BreakFree power tools in their Power T3 lineup have all won ACHR NEWS Dealer Design Awards. And they've also won an award for me that I didn't publish that just says these are great. The Bryan Orr, these are great awards. Our techs use them all the time and love them. The NTB7L power tube bender can help you create really high quality well-made
bends easily. There's seven size options with quick-connect mandrels letting you bend tubing from quarter inch to seven eighths OD. One button operation, just push a button and hold until you've got the bend you want. Let the tool pop it out for you and you'll get a perfect bend up to 90 degrees each time. The NTB7L won gold for best hand tool in the ACHR NEWS Dealer Design Awards in 2023. The NEF6LM is their lightweight battery powered flaring tool. Super light under three pounds easy to handle.
Flares copper in the standard sizes for residential and light commercial. HVAC soft tubing quarter inch to three quarter and those flare dies are included. Also just a quick note if you ever do have hard copper you can flare it so long as you heat and anneal it so heat it up to where it gets dark cherry let it cool off and then you can flare it. All you have to do is prepare the copper lock it in press a button and let the tool do the work for you. You don't even have to hold the button you just press it. And it won bronze for the 2022 ACHR NEWS Dealer Design Awards and the NTE11L
that is their power tubing expander often called a swedge tool comes with quick-connect heads that fit most common sizes from three-eighths to one inch and an eighth to swap them out depending on the size of copper you're using again only about three pounds and this one also won gold for the 2022 ACHR NEWS dealer Design Awards. Find out more about NAVAC's products and promotions including their power tubing tools at NAVACGlobal.com Riding with your guys is boring because they care so much and they try so hard and they know a lot of
the stuff already so it's hard finding I have to go like do these weird things to get them interested because they have so much of the other stuff down and I'm used to going in like let me show you superheat like oh that's cool I mean you solve those problems well you guys already know that it's refreshing right it's refreshing knowing that instead of online somebody's saying you don't need superheat or you guys embrace it and use it all the time it is nice if somebody wants to start with us it's overwhelming all of these different things we talk about where I recommend find a piece of equipment that you've installed find an expanded performance data start just figuring out what all those numbers mean
don't let it overwhelm you just keep looking at it every day and you start seeing different points and then say hey under these conditions get your wet bulb temperature inside wet bulb temperature outside or dry bulb temperature outside and your airflow and just start mapping out and then look and say hey what if I sped the airflow up what would happen with my capacity if I slowed the airflow down what would happen with my capacity if the day changed indoor and outdoor what would happen and then once you start figuring out how that one works you can start looking at different brands or different models and then you can start seeing oh hey if I have three different brands here under the same conditions would
they have the same capacity then you can start to see that they don't and that's what's cool is when you realize oh a three ton's not a three ton under different conditions and it's fun and you start getting there really it's like the secret like secret walls the secret text the secret things that people don't know you start unlocking these secret things which is really what Manual S is all about which like Tim De Stasio and I agree that the expanded performance data will do what that Manual S is doing with just a shortcut on it yeah system selection is a huge huge benefit of this thinking this type of thinking if you're in a
business where you're not doing any of that maybe you don't think about it but if you ever do your own sales or your own specking of equipment like you said I mean across brands even in things like ductless you can have some pieces of equipment that have completely different capacities under rated conditions than another under the same weather conditions and especially around latent if you're in a market where you're trying to remove a lot of moisture you need to specifically select your equipment for that not just at full capacity but also it turned down because some manufacturers are taking that really seriously doing some neat stuff around that and some are just ignoring it completely and just going for that
SEER number so there's a lot of things here once you start unlocking these little power -ups of understanding you can start to do better in system selection and commissioning and in service and that's the goal to be really really good at all three of those and frankly thank you for the nice compliments about our guys one thing about our guys is that they're just great humans they want to do the right thing they really care very enthusiastic but a lot of them are very new techs and they I wouldn't want them to select a piece of equipment they have to get good at some of these other things first our sales team I still work with them sometimes it's like why did you choose that a match over this match or creatures
of habit we're not always going to nail it but the more you understand this stuff and the more you read the manual the better off you're going to be and I think that's really the trifecta if you will you have to care you have to have good tools and take good measurements in order to get a good result not that you can't get an acceptable result it's easy to make people cold that's not hard but making it really efficient or dehumidifies really well and does everything it's supposed to do that's huge and then getting to the place that you understand it well enough that you can really really set it up properly and choose it properly that's the best situation because again if you're in middle America and your seasons aren't
that extreme compared to some other places you maybe can get away with it but if you're in the mountains or if you're living in Florida or you're in the arid desert of Death Valley you really need to know how to make these changes to the equipment it's cool when you start testing it but also when we see that that of those numbers for me numbers are just immediately give me anxiety and I have to remind myself to calm down what's cool though is where those numbers came from the story behind those numbers and when you get to go to some of the manufacturers they have these psychrometric rooms where they can make the conditions at anything that they want and they test every aspect of that equipment under those conditions
and then they record it and then they put it in this little graph for you so when you see those numbers it's like oh it's just numbers but those numbers come from people and equipment testing and for me like when I saw that firsthand I was like that is really cool and I told the manufacturers why don't you guys talk about this like let technicians know it's not just that we did numbers like an engineer just came up with these numbers like you guys are testing this and this room is amazing you can make it snow in this room and that's cool and like oh we don't want anybody to see our psychrometric room like it's exactly the same
as all your competitors it's the same room you have the same room it's the same AHRI testing points so talk about the show this but they don't and I have some footage that I can't share because I don't have permission but it's really cool when you see like where those numbers come from so if you ever get the chance I know you have but talking to you guys in the field if you ever get the chance to see a psychrometric room or a test facility it's absolutely incredible and talk to the people that do those numbers and the work I mean like oh yeah we tested this and we saw that and it's really fun to see where those numbers come from it is funny and I also encourage you to out there if you're a decision maker
in a business reward the companies that publish really good data with your business because there are some that do a lot better than others there are some who gate keep a lot of that data and there are some who I in the past at least suspected they may not have been testing the way they're supposed to there was one brand that across all of their tonnage matches it was 18 seer and a particular brand is 18 seer 18 seer I'm like no you're extrapolating you're taking one and then you're extrapolating and you're not actually testing at all those conditions but yeah most of the solid manufacturers that we all know do a pretty good job of that testing but then getting access to that data is another question and
then us actually using it to our benefit and our client's benefit is that's the main thing that's fun so 400 CFM per ton it's the scaffolding that can help us understand some things but it's not the whole answer any final words man just keep being curious keep learning if you find something that's overwhelming you then dive into it if it's overwhelming or scaring you just go like full in on it I'm going to learn everything about that for heat pumps I used to hate heat pumps and I was like I had a guy say well what do you like about him and I told him he's like sounds like you don't know enough about it I got mad it's like
oh yeah how do you tell he's like well go learn about it and come back and so once I learned everything about heat pumps I was like this is stupidly simple it's just like really simple I didn't understand it enough and then once I understood it it's like okay well there's still some things I don't like and there's some things I do like but now they understand it makes a difference so if we're talking about something like this and it's like oh you don't need to know that I understand that response I get that but also think man what if I just dive in and learned everything about it then you could be like you don't need that and actually have
all the data points to talk about so I think it's a fun thing but what the key is it's a trick because once you get into the numbers and seeing how all this stuff affects what we do you get addicted to it it's like oh man what else can we do with this what other problems can we solve yeah you get addicted to knowing what's actually going on it's very frustrating to be a tech and not know that and that's where we make a lot of excuses and do the whole like ah it's probably fine it's like guilty once in a while oh, all the time I still do it I mean like silly I the other day of my own system was a pound low something like that and it had frozen up and I defrosted and just went and put a pound and didn't
leak check it didn't it's about right subcool's at 10 fine whatever so like I get it and none of us are perfect at that but understanding how it works is makes our lives a lot better and ultimately the result is that we get fewer callbacks and we have happier clients and we actually deliver our promises better and better it's not about perfection it's about progress and companies and techs who do that well end up having happier customers in the long run it doesn't take a lot to teach people how to change a capacitor but it does take a lot to fix homes to
fix the actual air so when you start out yeah you're changing apart and I've made it run and that's great you did good but at some point you think if you've only done that for 20 years and you're thinking you're still that's like your whole thing think man what should I do to challenge myself to learn more and air psychometrics how the system works is a great point to start but even better if you're already young and you're like man I got these parts figured out I want more I want more here's a great point to jump into it's exciting when you get into this and that can unlock a lot more doors seeing technicians that get to
work for manufacturers and technicians that work for those representatives that solve problems other people couldn't solve or go work in the psychrometric room so it's interesting the doors that this can unlock in your future for sure Ty thanks so much thank you big thanks to Ty he's a great dude really is and it's good to have him here in central Florida at least for the time being working beside us at our company Kalos Services he's with the GRIT Foundation he has his own YouTube channel Love2HVAC and social media
follow him there but don't make him mad Ty is a lover not a fighter but he's also a fighter so don't screw with him you know what I'm saying and why would you want to anyway he's a great guy super cool dude again find out everything that we're doing at the GRIT Foundation over at the GRIT Foundation dot com we would always appreciate any support that you can provide and if you want to volunteer you want to have a grit camp please reach out at the GRIT Foundation dot com so I was talking to a country boy the other day he got upset because I wasn't
using the right pronouns he said his pronouns are he ha he should be yee ha I'm not sure he ha that's pretty old school anyway thanks for listening we'll talk to you next time on the HVAC School Podcast
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not your meter. Look,...
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to solve comfort...
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son, who has never lived...
In this short podcast episode, Bryan talks about electric heat and whether your service or maintenance procedure actually allows you to test every heat strip. In our climate, we use electric heat as auxiliary heat (as...
In this live stream, co-branded with Kalos, Bryan Orr sits down with Kalos refrigeration team members Christian Maitland and Alex Orr to talk about the realities of working on market refrigeration systems. The...